Subscribe to newsletter

Partners

  • Dinnissen BV

    International specialist in the world of bulk materials and process technology

  • VAC-U-MAX

    Pneumatic systems and support equipment for conveying, weighing and batching of dry materials

  • REMBE GmbH

    Developer and manufacturer of top of the range safety and measurement products

  • Hapman

    Leading manufacturer of conveyors and material handling equipment

  • Hosokawa Micron BV

    Systems for mechanical and thermal processing of dry and wet powders

  • Martin Engineering

    Systems for cleaner, safer and more productive handling of bulk materials

  • Hense Wägetechnik GmbH

    Individual advice and efficient solutions for the whole weighing technology process

  • Doubrava GesmbH & Co KG

    Doubrava is one of the world's leading names in industrial plant constructions

  • Dec Group

    Dec is a leading global manufacturer of powder handling and containment systems

  • Schutte-Buffalo Hammermill

    Designer and manufacturer of custom engineered size reduction machinery

  • Klinkenberg Zaanstad B.V.

    Klinkenberg BV is specialized in internal transport and bulk handling using screw conveyors

HomeSupplier NewsProduct NewsSmart tools for process cont ...

Product News

Smart tools for process control and weighing

15 May 2012 - 615 views

JOHANNESBURG - No matter how digital our world has become, most primary measurement in process plants are still analogue by nature only becoming digital somewhere down the line.

Take temperature for instance, the measurement starts out as voltage derived from joining two dissimilar metals together or from a change in resistance from metals like platinum, nickel or semiconductors or measuring infrared radiation.  Pressure, flow and force are mainly derived from physical deformation, measured with strain gauges in Wheatstone bridges or piezo-electric effects.  Levels can be measured in many, many ways but usually start out with an analogue measurement.  For this reason, in plant maintenance, commissioning and especially instrument workshops, process calibrators will always be indispensable.  With LCD graphics and the power of microprocessors, displays can be numeric with additional background information or even in the form of graphs with selectable time-bases, ideal for PID optimization trending or fault finding.

Accuracy
Because most field transmitters now have error limits of less than 0,5% the calibration equipment needs to be in the order of one magnitude higher, in other words 0,05%.  Modern single chip voltage references, 24 bit serial A/Ds and 20 bit D/As can be within full-scale limits of 0,01%.  The trick is to design input circuits with low-drift amplifiers for voltage and high stability shunts for current and resistance so that one gains the minimum additional error.  In linear or rotary measurement, most inputs are already digital by nature through encoders, whether inductive, optical or magnetic.  The calibrator’s function is then to measure or source frequency or counts.  This is referenced to the quartz time base used for the microprocessor, which is extremely accurate and, in some cases, where absolute real-time is needed, from GP satellites.

Practical Considerations
When a precision instrument like a process calibrator is going to be used in the field it better be rugged, both physically and electrically and have an acceptable battery life.  The housing needs to be thicker than normal,  have a rubber protection cover to withstand knocks and drops and be reasonably splash proof.  Besides the normal CE requirements, for electrical emission and noise immunity, inputs need additional surge protection with heavy duty MOVs and high speed fuses.  In spite of this we still see some units damaged when 230V is applied to the low level signal inputs!

Modern compact battery development and management has been spurred on in recent years from the demands of the cellphone and notebook industry.  We all recall the age of nickel-cadmium batteries going flat five minutes after the battery low warning light comes on.  This is probably the reason most manufacturers have stuck with the old, but field replaceable alkaline batteries.  The electronics industry solved this problem with high capacity metal-hydride batteries and the development of an intelligent ‘fuel-gauge’ chip.  This minute device monitors the voltage and measures the current in and out of the battery.  It also monitors the battery temperature for controlled high speed charging.  As a result of knowing the power (mA/hours) put in and used up, the battery indicator can be linear.  This technology has now been transferred into the handheld calibrator range with great success.

Loop Calibrators
In spite of many digital bus formats coming on to the market the 4 to 20 mA two-wire analogue system is still popular.  This 40 year old technique is readily understood by design engineers and plant technicians, requiring only a two-core cable to the sensor as the 4 mA minimum allows transmitter power to be taken off the signal line.  For protection and monitoring, if the signal drops below 3,8mA there is a cable open circuit or faulty electronics and if the signal goes above 22 mA there is likely to be a cable short circuit.  Loop calibrators are designed to measure the mA inline in a passive mode with the power supply from the control room or, by switching in a current limited 24 V supply, in active mode, powering up the transmitter directly without any connection to the control room.  This method is ideal for testing individual transmitters before commissioning.  Loop calibrators can also be used as simulators (with the transmitter out of the loop) in order to test the 4 to 20mA loop from the Control Room.

Process Calibrators
PLCs have the ability to measure analogue inputs as well as frequency and counts from encoders, proximity switches, some flow meters and other devices.  For these PLC based systems an ideal process calibrator should be able to measure and source milliamps, voltages, millivolts, frequency and counts.  Inputs and outputs need to be isolated from one another in order to test or calibrate transmitters.  For instance, inject mV whilst measuring the output 4 to 20mA.  On a two-wire transmitter this could be carried out without connection to the control room as the transmitter could be powered from the calibrator.  Where ground loops are a suspected cause of trouble during commissioning the calibrator could be set to mA in and mA out in tracking mode in order to check the circuit.  Should this clear the problem then a mA loop isolator could be installed permanently.  The frequency and counting functions should have selectable trigger levels for the inputs and scalable output voltage levels and programmable counting frequency from 0,1 to 1 kHz.

Thermocouple Calibrators
There are more than 15 different types of thermocouples whose choice depends on mV/°C, temperature range, corrosion resistance and cost.

The look-up linearising tables are quite extensive for each thermocouple type and require a large memory library.  As thermocouples only measure the difference in temperature between the hot junction and the cold junction, ambient compensation is necessary to either automatically measure the terminal temperature and add it to the difference (internal) or the cold junction temperature is measured and keyed into the calibrator (manual) where it is added.  It is due to uncertainties of measurement of this cold junction temperature that makes thermocouples unsuitable for ambient temperature measurement.  It is vitally important that the thermocouple extension cable is connected with the correct polarity.  If in doubt, twist the hot junction end of the extension cable together and warm them with a lighter provided the area is safe to do so.  The reading on the indicator or calibrator should increase.  Thermocouple calibrators should also be able to measure and source mV and mA for testing or calibrating temperature transmitters.

RTD Calibrators
Platinum and nickel have a very good correlation of resistance with temperature which makes them ideal for measuring temperature in the low to medium range.  Pt100 and N100 (100Ω@°0C) are industry standards with Pt500 and Pt1000 used where higher accuracies or resolution are needed.

Copper and semi-conductor RTDs do not have the same accuracy.  It is important that the line resistance or even change in resistance of the copper extension wires due to ambient temperature does not cause additional errors.  RTD calibrators must therefore be able to measure or source with a two-wire termination for direct connection or three-wire for longer leads.  Four-wire termination is the most accurate form of resistance measurement or simulation, as lead resistance does not affect the reading.  Measuring resistance accurately is relatively simple but it is extremely difficult to simulate (source) resistance accurately, with high resolution and to suit various forms of instrumentation inputs.  The RTD calibrator also requires the ability to measure and source mA in order to test or calibrate transmitters.

Pressure Calibrators
Calog Instruments approach to accuracy and flexibility in pressure calibrators is to make use of the technology coming on to the market from the manufacturers in digital output pressure transmitters.  With on-board microprocessors, temperature compensation and multi-point linearization it is standard to have 0,1 or 0,05% with a selection process.  With an addition time and price penalty these selected transmitters can be supplied with error limits better than 0,02% getting into the realm of deadweight testers!

Another real advantage of using these “pre-calibrated” products is that various pressure units can be connected and the model, range and serial number can be read into the calibrator for scaling and over range displays.  Therefore, a calibrator with a set of high accuracy transmitters to cover a wide selection of uses can be offered.  The mA measure and source facility allows the calibrator to be used for testing and calibrating pressure to mA transmitters, current to pressure convertors and, with tracking activated, give a mA output that follows a selected pressure range, ideal for testing or emergency replacement.

Loadcell (strain gauge) Calibrators
This product has been the company’s most exciting challenge to date:  how to build a full Wheatstone bridge analyser, an insulation tester and a process calibrator into one small, handheld device.  It took a year of conception, hardware and software development to achieve this and, amazingly it all worked beyond expectations and is now used extensively around the world.

By connecting a four or six-wire loadcell (or any strain gauge bridge circuit) to the calibrator resulted in having a full report including mV balance, in-and-output resistance and bridge balance in a few seconds.  By connecting leads to the screen and housing resulted in a 50 V insulation test between bridge, housing and screen.  With mV plus mA measure and source and excitation measurement, load cell systems can be measured, weighing systems electrically pre-calibrated and mAs injected into indicators or SCADA systems.

Conclusion
Calibrators are some of the most critical tools available to the engineer and technician.  They are also complex devices to design and manufacture, with practical considerations being as important as technical ones.